Three conditions separate a specifiable product from a marketing claim, and they apply to all passive house windows: the scope of the component certificate, the calculation conditions behind the whole-window U_w, and the thermal bridge at the installation junction. A certificate names one frame series, one glass U-value and one size basis; change the glass or the opening and the number stops describing what you are buying. Installation then adds a perimeter term, which is why an identical window can pass in one wall build-up and fail in another. Read a Passive House Institute certificate field by field and the pattern is consistent — the headline number is the least transferable thing on the page. This guide works through our own Component-ID 2557wi03 to show how the values are built, how they are lost, and which supplier checks and tender lines keep them intact once the window meets an actual opening.
What Passive House Windows Must Do That a Low U-Value Does Not
A passive house window has to satisfy three requirements at once, and only one of them is the number printed on the datasheet. The first is heat loss through the whole assembly: frame, glass, edge spacer and the area weighting between them, expressed as U_w. The second is interior surface temperature at design conditions — the frame and the glass edge have to stay warm enough that the room remains comfortable and moisture does not condense along the coldest line. The third is airtightness of the installed unit, because a good U-value on a leaky perimeter is a heat exchanger with a handle.
Aluminium makes the first two harder than any other common frame material. The metal conducts heat far better than timber or PVC, so the profile needs a thermal break — a non-metallic element that interrupts the path from the interior face to the exterior face. A break is the entry condition, not the finish line. The cavity behind it has to be insulated, the glazing pocket has to be deep enough for a serious insulating glass unit, and the sash has to close onto a compression gasket rather than rest against a brush strip. Where any of those is missing, the frame value stays high and the glass carries a load it was never meant to carry alone.
None of this is visible after handover, which is why a passive house window specification is largely a documentation exercise. The project needs a written value for the window at the project's own size, a written detail for the junction, and a certificate that ties both to a named product. All three can be checked before the order; almost none of them can be recovered afterwards.

Reading Passive House Certified Windows Documentation
The phrase passive house certified windows conceals a scope question, and scope is where most claims fail. The Passive House Institute certifies components. A component certificate names one product — in our case a window frame, series XML-S96 — and records the values the institute verified for that product under stated conditions. It does not certify a brand, a catalogue, or every unit that leaves a factory.
Our certificate is Component-ID 2557wi03, issued by the Passive House Institute in Darmstadt. The holder is Foshan Ximulong Home Technology Co., Ltd., the manufacturer behind the Aoslon export brand. That detail is not housekeeping: certificates are issued to manufacturing entities, and in a tender the entity named on the certificate has to be the entity that produces your order. A brand name on a website is evidence of neither.
Every field on the document carries a condition, so the useful exercise is to read them as a set rather than quoting the headline.
| Certificate field | What it establishes | Value as printed on the document |
|---|---|---|
| Certificate holder | The legal entity whose production was verified | Foshan Ximulong Home Technology Co., Ltd. |
| Component-ID | The register entry a certifier can look up | 2557wi03 |
| Component and series | What exactly is certified | Window frame, series XML-S96 |
| Whole-window U_w | Heat loss of the rated window at a stated glass value | U_w = 0.78 W/(m²K) with U_g = 0.70 W/(m²K) |
| Installed U_w | Heat loss including the validated installation | U_w,installed ≤ 0.85 W/(m²K) · validated installations 0.84 W/(m²K) |
| Frame U_f | Frame-only heat loss across the section range | U_f 0.71–0.75 W/(m²K) |
| Glazing edge Ψ | Linear loss where glass meets frame | Ψ-glazing edge 0.026 W/(mK) |
| Temperature factor f_Rsi | How warm the interior surface stays at design conditions | f_Rsi 0.77–0.78 |
| Efficiency class | Position within the scheme's class system | phB |
| Climate zone | Where the verified values apply | Cool, temperate |
| Validity | The date after which the entry must be re-checked | Valid until 31 Dec 2026 |
Two limits follow. First, the certificate covers the XML-S96 frame component — not the whole catalogue. It is a frame-component certification, never a whole-window certification; the U_w figure is calculated for a reference window at U_g 0.70. Second, U_w = 0.78 W/(m²K) is not a property of a window in the abstract. It is the result at U_g = 0.70 W/(m²K) under the certificate's size basis. Quote it without those conditions and you are quoting a number that cannot be compared with any other supplier's, because theirs was produced at a different glass value, a different size, or both.
The certificate and the full scope statement are reproduced on our certifications page, including the validity date and the entity it is issued to.
How the Passive House Window U Value Is Calculated
A passive house window u value is an area-weighted average with a linear term at the edge, and writing it out explains why single figures travel so badly between projects:
U_w = (A_g × U_g + A_f × U_f + l_g × Ψ_g) ÷ (A_g + A_f)
A_g and A_f are the glass and frame areas, l_g is the visible perimeter of the glass, U_g is the glass value, U_f the frame value and Ψ_g the linear loss at the glass-to-frame edge. Every term is measured or modelled at a defined size, so the output describes an assembly at that size — not a profile, and not a product family.
Three consequences follow for anyone comparing quotations. The frame fraction changes with size: a small opening has proportionally more frame, so U_w is typically worse at small sizes, as here, where U_f exceeds U_g. The frame value is itself a range, which is why U_f appears as 0.71–0.75 W/(m²K) rather than a single figure — the range covers the frame variants listed on the certificate. And the edge term only reproduces if the certified spacer is the spacer actually used; substituting a cheaper edge profile changes Ψ_g and quietly invalidates the result.
The glass side is where buyers concentrate and where the least leverage sits. U_g = 0.70 W/(m²K) is a demanding build, and reaching it is a question of cavity width, gas fill and coating — the subject of our Low-E glass guide. What the glass cannot do is compensate for a frame, which is why the two values have to be specified together. For the arithmetic of rated sizes and how U-factors are reported on either side of the Atlantic, see window U-factor explained.
The Installation Thermal Bridge: Ψ and f_Rsi at the Junction
U_w describes a window in a test frame, not a window in a wall. The junction adds a linear term around the perimeter of the whole unit, in the same form as the glazing edge term: installed heat loss rises with the length of that perimeter and with the Ψ of the detail. Our certificate states the outcome directly — U_w,installed ≤ 0.85 W/(m²K), with a validated installation at 0.84 W/(m²K).
Read those two numbers together and the validated detail sits 0.01 below the ≤0.85 criterion; change the junction and the installed value is recalculated, not assumed. One steel anchor that bridges the insulation, or a sill detail that lets the slab edge run past the frame, consumes it. The window has not changed and the certificate has not changed; the assembly has.
The same logic governs comfort. The temperature factor f_Rsi is set by the coldest point in the detail, not by the average across the window. The certified 0.77–0.78 therefore describes the window detail as tested; the wall junction is a separate detail with its own calculated f_Rsi, and if the insulation stops short of the frame that junction can fall below the limit and produce a cold interior corner where the reveal meets the wall. Condensation follows the coldest line, and the coldest line in a well-built wall is frequently a junction rather than a pane.
That is the argument for designing the junction before the window is ordered. Our BIM models carry the frame geometry and glazing build for coordination, and the installation detail that produced the validated 0.84 W/(m²K) is a drawing to be issued with the order rather than improvised on site. Where a project needs a different junction — a deep reveal, a curtain-wall interface, a renovation over an existing opening — the installed figure has to be recalculated for that detail, not assumed from the certificate.
PHI Component Certification vs PHIUS Certified Windows
PHIUS certified windows and PHI-certified components are not two spellings of one approval, and treating them as interchangeable is one of the more common tender errors. The Passive House Institute in Darmstadt runs a component certification scheme and publishes verified values under a Component-ID. PHIUS is a separate North American programme with its own certification route, its own modelling requirements and its own climate-specific criteria. A PHI component certification answers a narrow question — did this component meet this scheme's criteria under these conditions — and a PHIUS listing answers a different question in a different scheme.
Which one a project needs is decided by the certifier, the code or the client's brief, not by the supplier's preference. A US or Canadian project working to PHIUS criteria will usually need documentation in that programme's format; a European project working to PHI criteria will need the Component-ID. If a tender asks for "Passive House certification" without naming a programme, that ambiguity belongs in the request-for-information stage, because the two documents are not substitutable after award.
The same discipline applies inside our own documentation. Separate product lines carry separate certificates with separate scopes — a CE declaration for one sliding door type, an NFRC rating for one casement series, this PHI component certificate for the XML-S96 frame. None of them transfers to another series, and none becomes a Passive House result by association.
Where Certified Frames Fit: Cool Temperate and Beyond
The certificate names a climate zone because the values were verified for one. Cool, temperate is that zone, and phB is the efficiency class the component reaches within the scheme. Both are scope statements rather than quality rankings: phB describes where the component sits among the classes defined for that zone, and it does not convert into an equivalent label in another programme.
For a project in a hot-humid or hot-arid market the certificate still says something useful — the frame conducts little, the interior surface stays warm relative to a plain aluminium section, the edge detail is engineered rather than assembled. What it does not do is answer the dominant questions in those climates. Solar control, exterior condensation on the warm side, and the durability of the break under sustained thermal cycling are separate design problems, solved with the glass build and the junction rather than with the frame alone. A cool-temperate certificate is a defensible starting point in a hot climate; it is not a compliance argument for one.
Sound is the other axis a U-value does not describe. A passive house facade facing a road, a railway or an airport needs a glazing build chosen for its acoustic rating as well as its thermal one, and that is a separate specification covered in our guide to acoustic aluminum windows for commercial projects.
The mechanism involved is the one described on our thermal break sliding windows page: a polyamide strip interrupts the metal path, and the chamber around it carries drainage and seals. But the certificate applies to the XML-S96 frame component. Sliding assemblies are different products, and their performance is confirmed per project drawing rather than inferred from this certificate.
Top Custom Window Brands for Passive House Standards: How to Compare
Searches for top custom window brands for passive house standards return the same familiar names, generally ordered by marketing reach. For a specifier the ranking that matters is by evidence rather than brand: which legal entity holds a certificate, for which series, at which conditions, valid until when. One narrow, verifiable certificate is easier to specify — and easier to defend in a bid review — than a broad claim with no document behind it.
Eight questions produce a yes or no answer. Put them in writing, because a verbal confirmation has no standing in a submittal.
| Verification point | Question to put in writing | Evidence that satisfies it |
|---|---|---|
| Certificate holder | Which legal entity holds the certificate, and will that entity manufacture our order? | The certificate itself, with the brand relationship stated in writing |
| Component scope | Which series and which component does the certificate name? | Component-ID plus the series name, quoted back in the tender response |
| Calculation conditions | At what U_g and on what size basis was U_w derived? | The printed condition, plus a recalculation at project sizes |
| Installation | Which junction produced the validated installed value? | The junction drawing with its Ψ, not a generic site detail |
| Air permeability | Tested or declared, and at which class? | A test report or a declared class for that series on the datasheet |
| Validity | Will the certificate still be valid at delivery and completion? | The valid-until date, re-checked before award |
| Programme fit | Does the project's certifier accept PHI, PHIUS or both? | A programme-specific listing, not a cross-reference between schemes |
| Supporting data | Can the glass and spacer data behind the figures be produced? | IGU supplier data and spacer specification matching the certificate |
Two red flags are worth naming. The first is a U-value quoted without its glass condition; it is not a comparable number and should be sent back. The second is a certificate offered for a series that is not the series being supplied — a pattern that appears when a distributor carries several ranges and quotes the certified one as representative of all of them.
Specification Checklist for a Passive House Window Package
A tender for a passive house window package should specify outputs, not hopes. Each project input below needs a written deliverable before the order is placed, and each deliverable is auditable against the certificate.
| Project input | What the supplier must return in writing |
|---|---|
| Opening schedule, size by size | U_w at each actual opening size, not a sample or nominal size |
| Glass build and coating | U_g and solar factor of the specified IGU, plus the edge spacer type used |
| Frame series | Written confirmation that the series is XML-S96, or documentation for the alternative offered |
| Installation detail | Junction drawing with its Ψ and the resulting installed U_w |
| Airtightness interface | Membrane connection detail and confirmation that the frame is prepared for it |
| Anchors and brackets | Thermally broken bracket specification, spacing, and how penetrations are sealed |
| Finish | Powder coat or anodised specification, and confirmation that it changes no declared value |
| Documentation pack | Certificate copy, register extract, IGU data, packing list and inspection record |
| Delivery | Lead time of 25–45 days after deposit and frozen drawings; FOB Nansha, Shekou or Yantian |
The commercial terms follow from the same discipline. Units are made to drawings and rough openings, so nothing is quotable until the opening schedule is fixed. Lead time runs 25–45 days after deposit and frozen drawings for standard finishes and glass builds. MOQ is set per series and finish rather than as a single catalogue number, and several series can share a container without changing their individual minimums.
Common Claims That Do Not Survive Verification
Most of the failure modes in this article arrive as sentences in supplier emails. They are worth recognising in the form they actually take.
- "We are Passive House certified." A company cannot be. A named component, in a named series, under a named programme can be, and the certificate has to say so.
- "Our windows achieve 0.78." At U_g = 0.70 W/(m²K), on the certificate's size basis, for the XML-S96 frame. Anywhere else it is a different number describing a different assembly.
- "PHI and PHIUS are equivalent." They are separate programmes with separate criteria and separate documents, and the gap is not a formality.
- "The whole range is passive house." Our certificate covers the XML-S96 frame component. Other series require separate confirmation, per project, in writing.
- "Installed performance matches the window rating." It does not. Installation adds a perimeter term, which is why the certificate carries a separate installed value and a validated junction.
- "Certification is permanent." This one is valid until 31 Dec 2026. Tenders, awards and deliveries falling after that date need the current status re-checked.
- "It is rated, so it is certified." A rating and a certification are different instruments with different scopes, and a rated product elsewhere in a range does not certify the unit in front of you.
Frequently Asked Questions
Can the 0.78 W/(m²K) U_w be written straight into a tender?
Only with its conditions attached: U_g = 0.70 W/(m²K), the size basis stated on the certificate, and the series named as XML-S96. Written bare, the figure invites comparison with numbers produced at different glass values and different sizes, and it will not survive a technical review. Ask for a recalculation at your opening sizes alongside the quoted figure.
Are all Aoslon series Passive House certified?
No. Component-ID 2557wi03 covers the XML-S96 window frame component. It is a frame-component certification, never a whole-window certification: the U_w figure is calculated for a reference window at U_g 0.70, and it does not extend to the sliding, casement or door ranges. For any other series the position is confirmed per project against the drawings and the glazing build.
What is the difference between U_w and U_w,installed?
U_w is the window as a component: 0.78 W/(m²K) at U_g = 0.70 W/(m²K). U_w,installed adds the thermal bridge at the junction and is limited to 0.85 W/(m²K) on the certificate, with a validated installation at 0.84 W/(m²K). The difference between the two is the installation detail, and it is large enough to decide whether a project complies.
Do I need PHI or PHIUS certification for my project?
Whichever programme the project's certifier, code or client accepts. The two schemes have separate criteria and separate documentation, and one does not substitute for the other. Name the programme in the specification and ask suppliers for the corresponding document rather than a general statement about Passive House performance.
What happens when the certificate expires on 31 December 2026?
The entry has to be re-checked before it is relied on. Validity dates are printed on the document for a reason: a lapsed certificate is not evidence, even where the product itself has not changed. For projects with deliveries or completion after that date, request the current status in writing at tender stage and again before award.