Fire-Rated Windows: 20-120 Minute Ratings Explained | Aoslon

A fire rating on a window is not a property of glass, and it is not an upgrade you can add to a standard unit at the end of a quotation. It is the measured performance of a complete assembly: frame, glazing, seals, intumescent components and hardware, tested together as one specimen and classified for a stated period in minutes. What decides the outcome is the weakest element in that assembly, the standard it was tested to, the size and configuration of the tested specimen, and whether the frame-to-wall junction on your project matches the one in the report. Fire rated glass set into an untested frame carries no rating at all. This article explains what the classifications certify, how the 20, 45, 60, 90 and 120 minute grades differ, how glass and frame types pair, which standards apply on each side of the Atlantic, and which documents to demand before accepting a supplier's claim about fire rated windows and doors.

The narrower question is whether the specific assembly on the drawing has a classification report that covers it. Everything below serves that one test.

What a Fire Rating Actually Certifies

Fire performance reaches a project as two different documents, and confusing them is the most common error in fire rated window procurement. A glass maker can test a pane. Only a laboratory test on a complete specimen produces an assembly classification, and that classification names the frame profile, the glazing build-up, the seals, the intumescent components and the hardware present on the day.

Three criteria do the deciding. Integrity, written E, is the ability to stop flames and hot gases reaching the unexposed side, judged in the furnace by whether a cotton pad ignites and whether gaps open beyond a gauge. Insulation, written I, limits how far the unexposed face heats, measured at surface thermocouples. Radiation, written W, limits radiant heat flux at a stated distance. A classification is a combination: E 60 means sixty minutes of integrity, EI 60 integrity and insulation, EW 60 integrity with a radiation limit but no insulation requirement.

The distinction is not academic. A unit that survives the furnace still fails if the frame softens and the pane drops out of its rebate, if the bead releases at temperature, or if the perimeter sealant shrinks away from the wall. Aluminum loses most of its useful strength at temperatures a compartment fire reaches quickly, which is why an aluminum fire rated window is never a plain extrusion. It is extrusion plus reinforcement plus insulating layer plus intumescent material plus glass retention, tested as one item.

That is also why the same fire rated glass performs differently in two frames. The glass may be capable of an hour; the frame may be capable of twenty minutes. The number belongs to the weaker of the two.

The Rating Scale for Fire Rated Windows: 20, 45, 60, 90 and 120 Minutes

Minutes are a classification period, not a quality score. The grade comes from the compartment the assembly encloses: the code and the authority having jurisdiction set a required period for the wall, and the window is one element that has to reach it.

Two notations circulate. A European classification states the criterion and the minutes, such as EI 60. A North American schedule states the period in words, so a 1 hour fire rated window is a 60 minute fire rated windows requirement written differently. A 2 hour fire rated windows requirement is 120 minutes, and 90 minute fire rated windows sit between them at one and a half hours. When a specification mixes both notations, ask which standard the report was written against.

Nominal gradeOther ways it is writtenWhere it typically appearsWhat to confirm about the glass
20 minutesE 20, EW 20Door vision panels, light partitionsIntegrity only in most builds
45 minutesE 45, EW 45, EI 45Internal doors, corridor screensEI only where specified
60 minutes1 hour, E 60, EW 60, EI 60Commonly specified commercial wall periodE and EI both exist; name the criterion
90 minutes1.5 hour, E 90, EI 90Separations needing more than an hourFewer tested systems; check size and orientation
120 minutes2 hour, E 120, EI 120Plant rooms, parking, large compartmentsInsulation and hose stream more likely

Read the table as industry convention, not code determination. The grade is only meaningful with the criterion attached, and a specification that says only "one hour" has left the most expensive question unanswered.

Grades do not stack either: a 90 minute fire rated window is usually a separate classification from a longer furnace run or a formal extended-application assessment.

Cutaway diagram of a fire-rated aluminum window assembly showing intumescent seal, ceramic glazing and steel reinforcement in the frame
Every layer in the section is part of the tested specimen: steel reinforcement in the chamber, intumescent strip at the rebate, ceramic glazing, and the perimeter seal at the wall junction.

Fire Rated Glass: Wired, Ceramic and Intumescent Laminated

Fire rated glass is the material half of the problem, and three families cover most specifications.

Wired glass. Float glass with a wire mesh cast into it. The mesh holds fragments in place and slows the passage of flame, the product is inexpensive, and in most configurations it is integrity-only: a single wired pane does not insulate, so it suits E classifications where radiant heat on the protected side is acceptable. Some codes restrict where it may be used at all.

Ceramic glass. Usually a borosilicate, with a very low coefficient of thermal expansion, so it survives one face being heated while the other stays cool. It is clear, holds its appearance at temperature, and in multilayer builds reaches integrity and insulation.

Intumescent laminated glass. Layers bonded with an interlayer that foams into an opaque insulating char. The char holds the assembly together and slows heat transfer; depending on the number and thickness of the layers, the product reaches integrity alone or integrity with insulation. It is the most flexible family and the most dependent on the exact build-up.

The char also blocks the view, which matters where the pane doubles as a vision panel on an escape route: the assembly may hold, but nobody will see through it.

Tempered or heat-strengthened glass is not a fire rated product. It resists thermal stress and breaks into safer fragments, which is why it appears in safety glazing specifications, but neither property produces a fire classification.

None of the three carries a rating on its own. Fire rated glass describes a material's tested behaviour in a defined configuration; fire rated window describes an assembly that has been classified.

Fire Rated Glass Doors and Fire Rated Doors With Glass: A Different Assembly

Doors are not windows with a handle. Fire rated doors with glass are tested to door standards as a leaf hung in a frame with hinges, closer, latching and glazing already fitted, and the test records gaps, the hardware schedule and the maximum glazed area per leaf. Change the closer or widen the panel and you have a different assembly.

Fire rated glass doors carry two obligations a fixed window does not. The door has to close and latch by itself every time, because the rating assumes the leaf is shut when the fire starts; hold-opens must release on alarm, and the hardware that does the work is part of the tested set. The second is upkeep: in North America, NFPA 80 sets out installation and annual inspection practice for door assemblies, covering the glazing and the gaps. Treat that as industry context to confirm locally, not a clause that travels across borders.

Glazing in a door is also a smaller allowance than most people expect. Each tested leaf has a maximum glazed area and a defined position, and a panel running closer to the lock stile than the tested detail allows can invalidate the assembly even when every component is individually correct.

So quote door glazing as a set: leaf, frame, hardware and glass in one scope, with a report covering the combination. Windows and doors share a vocabulary of fire ratings and almost nothing else.

Frames: Why Fire Rated Window Frames Need a Tested System

The frame is where an aluminum system earns or loses its classification. Aluminum is a good structural material until it gets hot, and a compartment fire passes that point early.

  • Steel reinforcement. An insert sized to the internal chamber carries load after the aluminum softens and keeps the section from collapsing. Where it sits is a series decision drawn into the profile, not a site addition.
  • An insulating layer. A heat-resistant board or blanket inside the frame slows the temperature rise on the unexposed side, and in many systems it is what turns an E classification into an EI one.
  • Intumescent strips and mechanical retention. Strips at the rebate expand on heating to close gaps that open as components move, while a mechanical bead or retaining angle holds the glass after a conventional bead would have released.

The junction is part of the frame. A frame that passes in the furnace and leaks at the wall is not performing as classified: the perimeter gap, the fixing and the sealant sit inside the tested detail, and a site that substitutes sealant or leaves a wider gap has changed the assembly. Fire rated window frames therefore arrive with an installation detail that is a deliverable, not a site note.

Fixed glazing is common in this category because no operable sash means no lock, hinge or gasket line to fail, and the whole aperture can go to glass. Our aluminum fixed and picture windows are built as non-opening units to drawings and rough openings, the geometry fire-rated work usually starts from; any classification is established by the project's own test report, not by us.

Test and Classification Standards: EN 13501-2 and BS 476 Against UL 263 and ASTM E119

Two test cultures dominate export specifications, and a report from one does not answer a question asked in the other.

The European system. EN 1363-1 defines the furnace and heating curve. Element-specific standards then govern the specimen: EN 1634-1 for doors, shutters and openable windows, the EN 1364 series for non-loadbearing walls and curtain walling, and EN 16034, the product standard for fire and smoke door sets, which requires EN 1634-1 and EN 1634-3 evidence rather than acting as a test method itself. EN 13501-2 turns the data into the E, I and W classification, with a field of application stating the sizes, orientations and constructions the result may be applied to. Reading that field is the difference between a classification and a hope.

The UK legacy method. BS 476 Part 20 and Part 22 remain in use in the United Kingdom and in older specifications. They are legitimate test methods, but a BS 476 result is not automatically an EN 13501-2 classification; converting one to the other needs a formal assessment by a competent body.

The North American system. ASTM E119 is the assembly test and UL 263 the parallel UL standard, with NFPA 251 the legacy method. Door assemblies are tested to NFPA 252 or, where positive pressure is required, UL 10C, and glazed openings then face a hose stream test simulating a firefighting jet. Window assemblies have their own standard in NFPA 257, and NFPA 80 governs installation and maintenance of tested doors. The hose stream is what most often surprises exporters: an assembly can hold integrity for the full period and still fail when the jet hits.

The systems do not convert because the physics differs. Thermocouple placement, specimen size, furnace control, positive pressure and the hose stream all vary, as do the limits used to judge insulation. A report worth accepting names the laboratory and its accreditation, the standard and edition, the tested specimen with drawings, the time at which each criterion failed, and the classification with its field of application. Ask for all of it rather than the summary page, because the summary page carries almost none of the scope.

What to Ask a Supplier Before You Accept a Fire Rating

Most fire rating disputes are documentation disputes: the product performs as it performs, and the argument is whether anyone can show that the thing delivered is the thing tested. Eight questions separate a supplier who holds a classification from one who holds a brochure.

The questionA qualified answerA red flag
Which standard and edition was the assembly tested to?Element-specific test standard, edition, and classification standard"International standards", left unnamed
What is the report number, and who issued it?Accredited laboratory, number, date, copy on requestCover page only, expired certificate, logo without a number
What was in the tested specimen?Frame series, glazing build, seals, intumescent components, hardware"Our glass is certified", with no series named
What were the maximum tested size and configuration?Width, height, aspect ratio, mullions noted"Any size, the rating is in the glass"
Is it E, EI or EW?Criterion named, with minutes attached to each"One hour", criterion unstated
Does the scope cover my frame-to-wall junction?Detail matching the tested perimeter conditionGeneric sealant note, "not our scope"
Which hardware and closer were tested?Named schedule, substitutions formally assessed"Any equivalent hardware"
What is excluded from the field of application?Listed sizes, orientations, configurationsSilence, or "nothing is excluded"

The pattern is consistent: a real classification is narrow and a weak claim is broad. Suppliers who hold test evidence volunteer the limits, because the limits are what they can defend.

Two follow-ups suit export projects. Ask whether the field of application covers your elevation's orientation, since sloped glazing often falls outside a vertical classification. And ask who holds the original report: a distributor may be quoting another fabricator's test.

Specification Table: Matching Rating, Glass and Frame

The table structures the question; it does not replace the fire engineer's answer. The grade column is what is typically specified, to be confirmed against the code analysis before it enters a schedule.

LocationGrade typically specifiedGlass usually paired with itFrame requirementDocuments to request
Stair or lobby screenE 30 to EI 60Ceramic or intumescent laminatedSteel or reinforced aluminium frame tested with that glassEN 13501-2 classification, or an ASTM E119 or NFPA 257 report
Door vision panelMatched to the door assemblyCeramic or multilayer laminatedFrame rated as part of the door set, not separatelyDoor report, glazing scope, maximum glazed area
Opening near a property lineOften 1 or 2 hourInsulating fire glassThe exact frame series named in the reportReport including the wall junction detail
Shaft or atrium glazingEI, matched to the separationMultilayer laminated or ceramicRated frame with the fixing and seal from the specimenReport for the tested size and orientation
Plant room or parking1 or 2 hour, project-specificAn insulating build, E and IRated frame plus the hardware and closer scheduleReport plus hardware and closer schedule
Unit separation, mixed use60 minutes typicalIntumescent laminated or ceramicFrame series and reinforcement named in the reportReport naming frame series and glazing build

The grade column comes from the code analysis, and the documents column is what goes into the purchase order, because a rating that exists only in conversation does not survive handover.

Where our own scope sits is worth stating plainly. We manufacture thermal-break aluminum frames to drawings and rough openings in fixed, sliding, casement and door configurations. A fire-rated design with the reinforcement, rebate geometry and glass retention a classification requires is a project-specific route developed with the project's testing body; we do not supply a classified assembly. The classification itself is a project matter: assemblies are project-specific, and no rating is offered until the project's test report covers the exact assembly supplied.

That testing route belongs on the programme rather than in a sidebar. Production runs 25 to 45 days after deposit and drawing freeze on standard finishes and glass; project-specific fire evidence moves on its own track ahead of that, and a schedule that assumes otherwise will find the lead time at the wrong end of the job.

Where Fire Rated Glazing Changes the Whole Window Package

A fire classification does not sit beside the other performance requirements; it competes with them.

Thermal performance. Insulating fire glass and a reinforced frame rarely deliver the U-value of a high-performance unit. A frame carrying steel has less room for a thermal break, and the glass that insulates in a fire is not necessarily the glass that insulates against heat loss. The four performance dimensions behind that trade-off are set out in the commercial aluminum windows performance specs guide.

Air, water and structural design. Reinforcement and intumescent strips occupy chamber space that would otherwise carry drainage and pressure equalisation, so wind design and the fire detail are coordinated at the section drawing.

Weight and sightlines. Steel inserts, multilayer glass and heat-resistant board add mass and width. Sightlines widen, glass area shrinks, and the elevation changes with them.

Sequencing and interfaces. Rated units depend on a wall junction coordinated with the wall type that was tested; a different construction means the perimeter detail has to be assessed, not assumed. Inside a facade, the window sits in a larger assembly with slab-edge and spandrel conditions, and those interfaces are where classifications are most often lost. The comparison of window wall, curtain wall and storefront explains how those systems divide responsibility.

Impact resistance works the same way: a tested configuration, a report with a stated scope, no transfer between products. Our impact rated windows guide walks through that parallel logic.

Our own certificates cover CE marking to EN 14351-1:2006+A2:2016 for the TM2026 sliding door series, NFRC 102 for the E116 casement, a Passive House component certificate for the XML-S96 frame, and ISO 9001:2015 for the quality system. None covers fire resistance, and none is presented as fire evidence; the certifications page states the scope of each.

Frequently Asked Questions

Are 90 minute fire rated windows common?

Less common than 60 minute units, and usually tied to a specific separation rather than a general wall. Ninety minute fire rated windows appear where a compartment boundary demands more than an hour and the opening cannot be protected another way. Availability depends on the glass and frame combination, so confirm the tested size and field of application before scheduling.

Is a 2 hour fire rated windows requirement the same as 120 minutes?

Yes, the period is the same: two hours is 120 minutes. Ninety minute fire rated windows sit below that at one and a half hours, while 60 minute fire rated windows and 1 hour fire rated windows describe one requirement in two notations. The evidence does not carry over, though: a 2 hour fire rated windows specification needs a classification for that period with the criterion named.

Can the glass in a fire rated window be replaced on its own?

Not while keeping the rating. The classification belongs to the assembly, and the glazing build is part of the tested specimen: pane make-up, bead, setting blocks and intumescent components all appear in it. Replacing the glass with a different build, or the same nominal product from another maker, produces an assembly that has not been tested. A like-for-like replacement of the exact tested product, installed to the same detail, is the only defensible position.

Does a fire rating transfer from one window series to another?

No. A classification names the frame series, and the reinforcement, rebate geometry and glass retention are series-specific. Two frames that look similar on a section drawing can differ in exactly the dimensions the test measured. Ratings move between sizes within a stated field of application, not between series, and any extension has to come from the report or a formal assessment by the testing body.

Do residential projects need fire rated windows?

Sometimes, and the answer comes from the local building code and the fire review rather than from a supplier. Detached housing rarely specifies them; apartment buildings, mixed-use blocks and homes close to a property line can. Ask the authority having jurisdiction which openings are affected and what period applies.

Is 60 minute fire rated windows the same as 1 hour fire rated windows?

Yes, 60 minutes and one hour are the same period, which is why both phrasings appear in specifications. The variable is the criterion rather than the duration: an E 60 and an EI 60 are different products at the same period, and a schedule saying only "one hour" has not said which one it needs.